Skip to content
StandbyWise

Costs

Generac Fuel Consumption Chart

How much fuel a standby generator burns per hour, straight from Generac's spec sheets — at half load and full load, on natural gas and on propane. Guardian and Next Generation are charted separately because Generac publishes different numbers for the same kW size in each series; the two are never merged here. Ratings differ by fuel: a model's kW rating on propane is its headline size, and its natural-gas rating is lower (shown in the first column).

Turn these figures into a running cost

The Fuel & Running Cost Calculator uses exactly these verified consumption figures with your outage length and your local fuel price. We publish consumption here — what fuel costs near you is your input, not our guess.

Guardian Series

Size (LP / NG rating)EngineNG 50% (ft³/hr)NG 100% (ft³/hr)LP 50% (gal/hr)LP 100% (gal/hr)
10 kW / 9 kW460cc G-Force 400, 1 cylinder1011270.971.48
14 kW / 14 kW816cc G-Force 800, 2 cylinder1952561.813.07
18 kW / 17 kW816cc G-Force 800, 2 cylinder1692471.73.02
22 kW / 19.5 kW999cc G-Force 1000, 2 cylinder2283272.533.9
24 kW / 21 kW999cc G-Force 1000, 2 cylinder2033062.533.9
26 kW / 22.5 kW999cc G-Force 1000, 2 cylinder1883332.063.63

Sources

Next Generation Series

Size (LP / NG rating)EngineNG 50% (ft³/hr)NG 100% (ft³/hr)LP 50% (gal/hr)LP 100% (gal/hr)
10 kW / 9 kW459cc G-Force 400, 1 cylinder981320.941.6
14 kW / 14 kW817cc G-Force 800, 2 cylinder1892431.762.92
18 kW / 17 kW817cc G-Force 800, 2 cylinder1642351.652.87
22 kW / 21 kW997cc G-Force 1000, 2 cylinder2213112.453.71
24 kW / 22.5 kW997cc G-Force 1000, 2 cylinder1972912.453.71
26 kW / 24 kW997cc G-Force 1000, 2 cylinder1823162.053.95
28 kW / 25 kW997cc G-Force 1000, 2 cylinder1822972.233.97

Sources

Worked example: Guardian 22 kW over a 24-hour outage

The Guardian 22 kW (model G0070420) burns, per Generac's specifications, 228 ft³/hr of natural gas at 50% load and 327 ft³/hr at 100% load; on propane, 2.53 gal/hr at 50% and 3.9 gal/hr at 100%.

  • Natural gas, 24 hours at 50% load: 228 × 24 = 5,472 ft³
  • Natural gas, 24 hours at 100% load: 327 × 24 = 7,848 ft³
  • Propane, 24 hours at 50% load: 2.53 × 24 = 60.72 gallons
  • Propane, 24 hours at 100% load: 3.9 × 24 = 93.6 gallons

Real outages sit between the two load columns — the generator's load rises and falls with what is running in the house — so treat the 50% and 100% results as the floor and ceiling of the range, not a prediction. Multiply by your own per-unit fuel price in the fuel cost calculator to get dollars.

22 kW source

Notes and gaps — stated, not smoothed over